Flue gas analyzer Testo 310 set with printer
Flue gas analyzer Testo 310 set with printer
Temperature - TC Type K (NiCr-Ni)
Measuring range: -20 to +100 °C
Accuracy: ±1 °C
Resolution: 0.1 °C
Reaction time: < 50 s
Temperature (ambient temperature)
Temperature - TC Type J (Fe-CuNi)
Measuring range: 0 to +400 °C
Accuracy: ±1 °C (0 to +100 °C)
±1.5 % of mv (> 100 °C)
Resolution: 0.1 °C
Reaction time: < 50 s
Temperature (flue gas)
Flue gas O₂
Measuring range: 0 to 21 Vol.%
Accuracy: ±0.2 Vol.%
Resolution: 0.1 Vol.%
Reaction time t₉₀: 30 s
Flue gas Draught
Measuring range: -20 to +20 hPa
±0.03 hPa (-3 to +3 hPa)
Accuracy :±1.5 % of mv (Remaining Range)
Resolution: 0.01 hPa
Flue gas degree of effectivity, Eta (calculated)
Measuring range: 0 to 120 %
Resolution: 0.1 %
Flue gas loss (calculated)
Measuring range: 0 to 99.0 %
Resolution: 0.1 %
Flue gas CO₂ calculation (calculated from O₂)
Measuring range: 0 to CO₂ max (Display range)
Accuracy: ±0.2 Vol.%
Resolution: 0.1 Vol.%
Reaction time t₉₀: < 40 s
Pressure measurement
Measuring range: -40 to +40 hPa
Accuracy: ±0.5 hPa
Resolution: 0.1 hPa
Flue gas CO (without H₂-compensation)
Measuring range: 0 to 4000 ppm
Accuracy: ±20 ppm (0 to 400 ppm)
±5 % of mv (401 to 2000 ppm)
±10 % of mv (2001 to 4000 ppm)
Resolution: 1 ppm
Reaction time t₉₀: 60 s
Ambient CO
Measuring range: 0 to 4000 ppm
Accuracy: ±20 ppm (0 to 400 ppm)
±5 % of mv (401 to 2000 ppm)
±10 % of mv (2001 to 4000 ppm)
Resolution: 1 ppm
Reaction time: 60 s
incl. battery and calibration protocol for the measurement of O2, CO, hPa, and °C; IR printer (0554 3100); probe 180 mm with cone; case; mains unit incl. cable; silicon hose for pressure measurement; particle filter 5 off; 2 rolls spare thermal paper for the printer.
VSKU: 1014000012